Item number ETHER-MODUL-4X-DI-3

Ethernet I/O Module with 4x DI, 4x DO, PoE and RS-232/485

CPU 80186-80 MHz or compatible
4 x Digital Input, Dry Contact
4 x Digital Output, Open Collector
10/100 Base-TX RJ-45 Ethernet
2x RS-232, 1x RS-485 Serial
PoE IEEE 802.3af Class 1
Watchdog Timer
Metal Casing, Wall Mounting
12-48VDC or PoE Power Input
102 x 29 x 125 mm (WxLxH)
-25/+75C (special components required)

418.08 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

CPU 80186-80 MHz or compatible
Flash 512 KB ; Erase unit is one sector (64 KB) ;100,000 erase/write cycles
Installation Wall mounting
Type Open CollectorDry Contact
Operating Temperature -25 ~ +75 °C
Watchdog Timer Yes
Status 1 x Power/PoE
Ports 10/100 Base-TX, RJ-45 port (Auto-negotiating, auto MDI/MDI-X, LED indicator)2 x 3-wire RS-2321 x 5-wire RS-2321 x RS-485
Consumption 2.2 W
Dimensions (mm) 102 mm x 29 mm x 125 mm (W x L x H)
Storage Temperature -40 ~ +80 °C
Humidity 5 ~ 90% RH, Non-condensing
Channels 4
Powered from Terminal Block +12 ~ 48 VDC
Sink/Source (NPN/PNP) Sink (NPN)Source, Common Ground
ON Voltage Level +3.5 ~ +30 V
OFF Voltage Level +1 V max.
Load Voltage 30 VDC, max.
Load Current 100 mA, max.
Baud Rate 115200 bps Max.
Parity None, Even, Odd, Mark, SpaceNone parity is required when using 8 data bits and 2 stop bits on COM1/COM2.
Data Bit 7, 8: for COM1 and COM25, 6, 7, 8: for COM3 ~ COM4
Stop Bit 1, 2: for COM1 ~ COM4
Casing Metal
Powered from PoE IEEE 802.3af, Class 1
EEPROM 16 KB; Data retention: 40 years; 1,000,000 erase/write cycles.
SRAM 512 KB
Bias Resistor Yes, 1 KΩ
Node Address 254 (max.)

Industrial Ethernet I/O Module

This Ethernet I/O module provides digital input and output channels together with serial communication ports for industrial automation and remote monitoring. It is designed for reliable operation in demanding environments and can be powered directly from the network via PoE.


4x Digital Input · 4x Digital Output · PoE IEEE 802.3af · -25 to +75°C


Key Features

  • Digital I/O - 4 dry contact inputs and 4 open collector outputs for direct field connection
  • Serial Interfaces - 2x RS-232 and 1x RS-485 ports for connecting legacy devices
  • Power over Ethernet - IEEE 802.3af Class 1 support removes the need for a separate power supply
  • Watchdog Timer - automatically restarts the module if it stops responding
  • Rugged Metal Housing - suitable for wall mounting in industrial environments


Typical Applications

The module fits into automation and monitoring systems where digital signals and serial devices need to be integrated with an Ethernet network.

  • Factory automation
  • Remote monitoring and control
  • Building management systems
  • Machine interfacing


A robust and flexible choice for connecting digital I/O and serial devices to an Ethernet network.