Item number ETHER-MODUL-DIGIT-INPUT-14

Ethernet I/O Module with 6 x Digital Input, 6 x Relay Output, PoE

6 x Digital Input, Wet Contact
6 x Relay Output, Form A 5A
2 x RJ45 10/100 Switch Ports, LAN Bypass
Modbus TCP/UDP, MQTT, REST, SNMP, HTTP
Web interface configuration
IF-THEN-ELSE logic, timer, schedule
Isolation Ethernet 1500VDC, I/O 3000VDC
PoE IEEE 802.3af Class 2
12-48VDC terminal block power
76 x 120 x 38 mm
25 to 75C (special components required)

310.88 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type Wet ContactPower Relay, Form A (SPST N.O.)
Operating Temperature 25 to +75°C
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet, I/O
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
Consumption 3.9 W (max.)
Dimensions (mm) 76 x 120 x 38 (W x L x H)
Storage Temperature 30 to +80°C
Humidity 10 to 90% RH, Non-condensing
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal ±8 kV Air for random point
Channels 6
Input Impedance 10 kΩ
Overvoltage Protection +70 VDC
Safe Value Programmable
Powered from Terminal Block +12 to +48 VDC
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +10 to +50 VDC
OFF Voltage Level +4 VDC (max.)
Power on Value Programmable
Protocol Modbus TCP, Modbus TCP/TLS, Modbus UDP, MQTT, Rest API, CoAP,LwM2M, SNMP, SMTP, SNTP, HTTP/HTTPS
Powered from PoE Yes, IEEE 802.3af, Class 2
Contact Rating 5 A @ 250 VAC/24 VDC (Resistive Load)
Operate Time 10 ms (max.)
Release Time 5 ms (max.)
Electrical Endurance 10^5 ops.
Mechanical Endurance 2 × 10^7 ops.
Frequency 100 Hz
Function • Web Interface for Configuration• IF-THEN-ELSE Logic operation• I/O channel monitoring and control• Timer operation• Schedule operation• Internal Register operation
2-way Isolation Ethernet: 1500 VDCI/O: 3000 VDC
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±2 kV for Power Line
Max. Counts 4,294,967,295 (32-bit)
Min. Pulse Width 5 ms
LAN bypass Yes
Access Control ID, Password and IP Filter

Ethernet I/O Module

This Ethernet I/O module is designed for remote monitoring and control in industrial applications. The module combines digital inputs and relay outputs with a flexible web interface for configuration and logic control. It is well suited for automation tasks that require reliable communication and rugged operation.


6 x Digital Input · 6 x Relay Output · PoE IEEE 802.3af · Modbus TCP/MQTT


Features that simplify integration

  • Web Interface - easy setup without extra software
  • IF-THEN-ELSE Logic - local automation without a PLC
  • Timer and Schedule - time-based I/O operations
  • LAN Bypass - maintains network connection during power loss
  • Dual Isolation - protects against noise and voltage fluctuations


Application areas

The module suits monitoring and control tasks across industrial and building automation systems.

  • Remote control of pumps and motors
  • Alarm system monitoring
  • Automated building management
  • Integration into SCADA systems


A rugged and flexible solution for reliable I/O control over Ethernet.