Item number BACNE-IP-MODBU-TCP-2

BACnet/IP to Modbus TCP Gateway, 32 Stations, DIN-Rail

Modbus TCP Client, up to 32 stations
BACnet objects: AI, AO, AV, BI, BO, BV
MSI, MSO, MSV supported
Converts 180 DI, DO, AI and AO points
BIBBs: DS-RP-B, DS-RPM-B, DS-WP-B
DS-WPM-B, DM-DDB-B, DM-DCC-B, DM-RD-B
1 x RJ-45, 10/100Base-TX
Metal casing, DIN-Rail mount
10-30VDC, 5W @ 24VDC
33 x 120 x 116 mm
-25 to 75C (special components required)
Humidity 10-90% RH, non-condensing

624.44 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail
Operating Temperature 25 ~ +75 °C
Status Power (1), BACnet/IP Status (1), BACnet/IP Net(1), Modbus TCP TxD/RxD/Link (3)Ethernet LED Ethernet Status (RJ-45) (2)
Ports 1 x RJ-45, 10/100Base-TX
Input Range +10 ~ +30 VDC
Consumption 5 W @ 24 VDC
Dimensions (mm) 33 x 120 x 116
Storage Temperature 30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Protocol Modbus TCP Client(Supports up to 32 stations)
Casing Metal
Objects AI, AO, AV, BI, BO, BV, MSI, MSO, MSV(Convert modbus 180 DI, 180 DO, 180 AI and 180 AO)
BIBBs DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-RD-B

BACnet/IP to Modbus TCP Gateway

This gateway connects BACnet/IP networks with Modbus TCP devices, allowing up to 32 Modbus stations to be integrated into a BACnet management system. It is commonly used in building automation projects where existing Modbus equipment needs to be made available to an overarching BACnet system.


Modbus TCP Client, up to 32 stations · BACnet objects: AI, AO, AV, BI, BO, BV, MSI, MSO, MSV · 1 x RJ-45 10/100Base-TX · DIN-Rail mounting


Features for reliable integration

  • Modbus TCP Client -communicates with up to 32 Modbus stations
  • Full BACnet object support -converts up to 180 DI, DO, AI and AO points
  • BIBBs support -ensures interoperability with BACnet systems
  • Robust metal casing -protects electronics in industrial environments
  • DIN-Rail mounting -easy installation in control cabinets


Applications in building and industrial automation

The gateway is well suited for projects where Modbus-based devices need to be integrated into a BACnet network.

  • Building automation (HVAC, lighting)
  • Integration of Modbus meters and sensors
  • Industrial control systems
  • Energy monitoring


A reliable and flexible solution for bridging Modbus and BACnet systems.