Item number 16-CHANN-RTD-INPUT-2

16-Channel RTD Input Module, Ethernet, Modbus TCP/UDP, MQTT

16 x RTD Input (Pt100, Ni120, Cu50, Cu100)
16-bit Resolution
Accuracy +/-0.05% FSR (Normal Mode)
Sampling up to 90 Hz (Fast Mode)
2 x RJ45 10/100 Switch Ports, LAN Bypass
Modbus TCP/UDP, MQTT, SNMP V2c
Isolation Ethernet 1500VDC, I/O 3000VDC
Open Wire Detection, 3-wire RTD Lead Elimination
Metal Casing, DIN-Rail / Wall Mount
10-48VDC Power Input
-25 to +75C Operating (special components required)
31 x 159 x 137 mm (W x L x H)

873.68 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

CPU 32-bit ARM
Resolution 16-bit
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal±8 kV Air for Random Point
Channels 16
Accuracy Normal Mode: ±0.05 % of FSR (25℃)Fast Mode: ±0.1 % of FSR (25℃)
Sampling Rate Normal Mode: 1.5 Hz (per channel)Fast Mode: 90 Hz (per channel)
Sensor Type Pt100, Ni120, Cu50, Cu100
2-way Isolation Ethernet: 1500 VDCI/O: 3000 VDC
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±2 kV for Power Line
Built-in Web Server Yes

RTD Input Module

This RTD input module is designed for precise temperature measurement in industrial environments and supports up to 16 channels with multiple sensor types. The module integrates easily into existing Ethernet networks and provides reliable data acquisition for automation and monitoring tasks.


16 Channels · 16-bit Resolution · Modbus TCP/UDP · -25 to +75°C


Features that ensure stable operation

  • Multiple sensor types - supports Pt100, Ni120, Cu50 and Cu100
  • High accuracy - precision of ±0.05% of FSR in normal mode
  • Open wire detection - automatically identifies broken sensor connections
  • 3-wire RTD compensation - eliminates errors from lead resistance
  • LAN bypass - maintains network connection during power loss


Applications in industrial systems

The module is well suited for temperature monitoring in production facilities, machine rooms and process industries, where stable measurements are essential.

  • Temperature monitoring in industrial processes
  • Integration into SCADA and automation systems
  • Distributed data acquisition via Ethernet
  • Monitoring of cooling and heating systems


A robust and precise choice for reliable RTD-based temperature measurement in industrial networks.