Item number CANOP-POWER-METER-INTER-2

CANopen Power Meter Interface, 2-Loop, RS-485 Modbus RTU, 12-48VDC

2-channel power meter interface
Wiring: 3P4W, 3P3W, 1P2W, 1P3W
Input voltage 10-500V, 50/60Hz
True RMS V/I, kW, kWh, kVA, PF
1 second data update rate
2 x Power Relay output, 5A
1 x RS-485, Modbus RTU
Baud rate up to 115200
3000VDC isolation
12-48VDC, 2W consumption
33 x 100 x 127 mm
-20 to 70C (special components required)

281.40 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Input Frequency 50/60 Hz
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops 3-phase: 11-phase:3 @ 1P2W-1CT1 @ 1P3W-2CT
Input Voltage 10 ~ 500 V
Input Current Supports 333 mV output CTs; actual current range depends on CT’s primary rating

CANopen Interface

This CANopen interface is designed to measure and monitor electrical power parameters via connected current transformers. The device converts measurements into Modbus RTU data over RS-485 and is well suited for industrial energy monitoring.


2 channels · 10-500V input · RS-485 Modbus RTU · DIN-rail mounting


Features that make the difference

  • True RMS measurement - accurate voltage and current readings
  • Multiple wiring configurations - supports 3P4W, 3P3W, 1P2W and 1P3W
  • Power relay outputs - 2 channels for alarming or control
  • Galvanic isolation - 3000 VDC isolation protects the system
  • Flexible communication - RS-485 with adjustable baud rate and data format


Application areas

The interface is suited for industrial environments where power and energy consumption must be monitored accurately and reliably.

  • Energy metering in production facilities
  • Monitoring of electrical panels
  • Building automation and energy management
  • Integration with CANopen-based systems


A robust and accurate solution for energy measurement in industrial applications.