Item number ETHER-ANALO-INPUT-MODUL-7

Ethernet Analog Input Module, 8-CH Isolated, PoE, Modbus TCP/UDP

8 x Isolated Analog Input, 16-bit
Voltage/Current, Jumper Selectable
4 x Isolated Digital Output
2500VDC I/O Isolation
2 x RJ45 10/100 Switch Ports
PoE IEEE 802.3af Class 1
Modbus TCP, Modbus UDP
Built-in Web Server
Communication Watchdog Timer
12-48VDC or PoE Powered
76 x 120 x 42 mm
-25 to 75C (special components required)

403.34 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Isolation ±400 VDC, Virtual Channel to Channel Isolation
PoE yes
Type Isolated Open CollectorVoltageCurrent
Operating Temperature 25 ~ +75 °C
Resolution 16-bit
Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V±20 mA, 0 ~ 20 mA, 4 ~ 20 mA(Jumper Selectable)
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet, I/O, PoE
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
Consumption 4.4 W (max.)
Dimensions (mm) 76 x 120 x 42 (W x L x H)
Storage Temperature 30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Overload Protection 1.4 A
Short-circuit Protection Yes
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal ±8 kV Air for random point
Channels 8 (Differential)4
Accuracy Normal Mode: ±0.1%Fast Mode: ±0.5% or better
Sampling Rate Normal Mode: 10 Hz (total channels)Fast Mode: 50 Hz (total channels)
Input Impedance Voltage: 2 MΩCurrent: 125 Ω
Overvoltage Protection 240 Vrms+60 VDC
Safe Value Programmable
Powered from Terminal Block +12 ~ +48 VDC
Sink/Source (NPN/PNP) Sink
Load Voltage +5 ~ +50 VDC
Load Current 700 mA/Channel
Power on Value Programmable
Overcurrent Protection 50 mA at 110 VDC (max.)
Individual Channel Configuration Yes
Protocol Modbus TCP, Modbus UDP
Open Wire Detection For 4 ~ 20 mA only
Powered from PoE IEEE 802.3af, Class1
Common Voltage Protection ±200 VDC
2-way Isolation I/O: 2500 VDC
EFT (IEC 61000-4-4) ±2 kV for Power Line
Surge (IEC 61000-4-5) ±2 kV for Power Line
LAN bypass Yes
Access Control ID, Password and IP Filter
Built-in Web Server Yes

Analog Input Module

This analog input module is designed for industrial data acquisition over Ethernet and supports both voltage and current signals. The module combines isolated analog inputs with digital outputs, making it suitable for demanding automation tasks.


8 isolated analog inputs · 16-bit resolution · PoE support · Modbus TCP/UDP


Features that ensure stable operation

  • Isolated channels - 2500 VDC isolation protects against noise and voltage spikes
  • Flexible signal type - jumper-selectable voltage or current per channel
  • PoE powered - receives both data and power over a single Ethernet cable
  • Built-in web server - easy configuration and monitoring directly in the browser
  • Watchdog timer - monitors communication and ensures automatic recovery from errors


Use in industrial systems

The module fits applications where analog sensor signals need to be reliably collected and forwarded over an Ethernet network.

  • Process monitoring in production facilities
  • Temperature and pressure measurement via 4-20 mA sensors
  • Remote data acquisition in automation systems
  • Integration into SCADA and Modbus-based solutions


A robust and flexible choice for reliable analog data acquisition in industrial Ethernet networks.