Item number CO2-PM2-TEMPE-HUMID-2

CO2/PM2.5/Temperature/Humidity Sensor with WiFi, Ethernet and RS-485

CO2, PM1/2.5/10, Temp and Humidity
CO2 range 0-9999 ppm (NDIR)
PM2.5 range 0-1000ug/m3, laser type
Temp range -10 to +50C, +/-0.6C
Humidity 0-100% RH, +/-5% RH
Data logger up to 450,000 records
Real time clock built in
WiFi 802.11 b/g/n, Ethernet, RS-485
Modbus RTU/TCP, DCON, MQTT
IP filter whitelist and web password
12-48VDC, ceiling/wall mount, IP20
0-50C operating (special components required)

690.10 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Alarm PM1/PM2.5/PM10/CO2/RH/Temperature
Installation Ceiling Mounting/Wall Mounting
Operating Temperature 0 ~ 50°C
Resolution 0.1°C1μg/m31 ppm0.1% RH, Non-condensing
Range Calculated using temperature and relative humidity10 ~ +50°C0 ~ 100% RH, Non-condensing0 to 1,000μg/m3 ( Laser Type)0 to 9999 ppm (NDIR)
Encryption WEP, WPA and WPA2
Real Time Clock Yes
Ports 1 x RS-4851 x Ethernet10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators)
Consumption Non-PoE: 2.4 W (Max.)PoE: 2.6 W (Max.)
Dimensions (mm) Ø 150 x 53 (Ø x H)
Storage Temperature 30 ~ +75°C
Humidity 10 ~ 90% RH, Non-condensing
Channels 1 x Form A, SPST30 VDC @ 16 A or 250 VAC @ 16 A
Accuracy ±0.6°C±5% RH, Non-condensing± 10% of FSR.±40 ppm ±3% of measured value
Response Time 120 seconds1 seconds
Powered from Terminal Block +12 ~ +48 VDC
Protocol DCON and Modbus/RTU (RS-485)Modbus TCP(Ethernet, Wi-Fi) and MQTT(Ethernet)
Mode Infrastructure & Limited AP
Ingress Protection Rating IP20
Antenna 1 dBi (PCB Antenna)
RX Sensitivity 95.7 dBm @ 1 DSSS, -74.0 dBm @ 54 OFDM
Transmission Distance (LoS) 50 meters (LOS)
Output Power 18 dBm @ 1 DSSS, 14.5 dBm @ 54 OFDM
Security IP filter (whitelist) and Password (web)
Standard Supported IEEE 802.11 b/g/n
Data Logger Yes, up to 450,000 records
Life Time 15 years10 years5 years, Customer has to replace the filter patch.
Warm-up Time 20 seconds5 minutes
Sizes 0.3μm, 0.5μm, 1μm, 2.5μm, 5μm, 10μm

Air Quality and Climate Multisensor

This multisensor simultaneously measures CO2, PM1/PM2.5/PM10, temperature and relative humidity. It is well suited for indoor air quality monitoring in offices, schools and industrial environments where accurate and reliable data are essential.


CO2 0-9999 ppm · Laser PM sensor · WiFi & Ethernet · Data logger 450,000 records


Features that make the difference

  • NDIR CO2 sensor - high accuracy with a 15-year lifetime
  • Laser-based PM measurement - detects particles from 0.3 to 10 μm
  • Built-in data logger - stores up to 450,000 records
  • Flexible connectivity - WiFi, Ethernet and RS-485 with Modbus/MQTT
  • Real time clock - ensures accurate timestamping of all data


Applications

The sensor is designed for fixed ceiling or wall mounting, providing continuous air quality monitoring.

  • Office environments and meeting rooms
  • Schools and educational institutions
  • Industrial process control
  • Building automation and BMS integration


A complete solution for reliable real time air quality and climate monitoring.