Item number LIQUI-LEAK-DETEC-RS

Liquid Leak Detector with RS-485, Cable/Probe Sensing, Relay Output

Liquid leak and cable-break detection
RS-485, Modbus RTU or DCON protocol
1 x Signal Relay output (Form A, SPST)
Buzzer alarm, mutable via push button
Power and alarm status indicators
Sensitivity 26 - 580 KOhm, adjustable
Max. cable length 500 meters
Baud rate 1200 - 115200 bps
Reverse polarity protection
10-30VDC, 1.5W max.
80 x 70 x 28 mm
-25 to 75C (special components required)

65.66 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Alarm For both liquid leak detection and cable-break detection.
Installation Wall Mount
Operating Temperature 25 ~ +75 °C
Status 1 as Power Indicator1 as Alarm Indicator
Buzzer Yes.Can be muted by a push button.
Ports 1 x RS-485
Input Range 10 ~ 30 VDC
Consumption 1.5 W Max.
Dimensions (mm) 80 x 70 x 28 (W x L x H)
Storage Temperature 30 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±8 kV Air for Random Point
Channels 1
Baud Rate Software Configuration: 1200 ~ 115200 bps
Sensor Type Probe for point detection or Cable for line detection
Data Format (N,8,1), (O,8,1), (E,8,1), (N,8,2)
Protocol Modbus RTU or DCON
EFT (IEC 61000-4-4) ±4 kV for Power
Relay Output Signal Relay, Form A x1, SPST0.25 A @ 250 VAC0.5 A @ 125 VAC2 A @ 30 VDC
Liquid Type Water, 2uS/cm
Max. Cable Length 500 meters Include Liquid Leak Detection Cable and Extended Cables.
Sensitivity Range 26 KΩ ~ 580 KΩ (adjustable by rotary switch)
Cable-break Detection Yes.For sense cable CA-LLD-DC100X-Lxxx only.

Liquid Leak Detector

This liquid leak detector is designed to monitor floors, server rooms and technical installations for water leakage. The device supports both point detection via probe and line detection via sensing cable, and integrates directly into industrial monitoring systems through RS-485.


RS-485 Modbus RTU/DCON · Cable and probe detection · Relay output · Up to 500 m sensing cable


Features for reliable monitoring

  • Dual detection methods - supports both probe for point detection and cable for line detection
  • Cable-break detection - detects a break on the connected sensing cable
  • Adjustable sensitivity - set via rotary switch from 26 to 580 KOhm
  • Audible alarm with mute function - buzzer can be muted with a push button
  • Robust communication - RS-485 with Modbus RTU or DCON protocol and adjustable baud rate


Application areas

The product is well suited for monitoring areas where water damage can have serious consequences.

  • Server rooms and data centers
  • Technical installation rooms
  • Raised floors with piping
  • Storage areas with sensitive equipment


A reliable solution for early detection of liquid leaks and cable breaks in critical areas.