Item number RS-485-REPEA-MODUL-4

13-ch Isolated (Sink, NPN, 3.5~30 VDC) DO Module, RS-485, DCON

13 x Open Collector output channels
Sink type, Load 3.5-50VDC
Load current 100mA/channel
1 x RS-485 port, DCON protocol
Baud rate 1200-115200 bps
Programmable watchdog timer
Programmable power on/safe value
Isolation 3750 Vrms
Reverse polarity protection
10-30VDC power input
72 x 123 x 35 mm
-25 to 75C (special components required)

127.30 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type Open Collector
Operating Temperature 25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Ports 1 x RS-485
Input Range +10 ~ +30 VDC
Consumption 1.0 W
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
Reverse Polarity Protection Yes
Intra-module Isolation 3750 Vrms
ESD (IEC 61000-4-2) ±2 kV Contact for Each Terminal±4 kV Air for Random Point
Channels 13
Safe Value Programmable
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 ~ +50 VDC
Load Current 100 mA/Channel
Power on Value Programmable
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol DCON
EFT (IEC 61000-4-4) ±2 kV for Power Line

Repeater Module

This repeater module is designed to extend and strengthen communication signals in industrial RS-485 networks. The module is used to connect and control digital output channels over long distances with high reliability. It is well suited for demanding requirements in electrically noisy environments.


13 channels · RS-485 DCON · 3750 Vrms isolation · Programmable watchdog


Features that ensure stable operation

  • Open Collector output -allows flexible control of 13 independent channels
  • Galvanic isolation -3750 Vrms protects against noise and voltage spikes
  • Programmable watchdog -ensures automatic recovery from communication faults
  • Power on and safe value -predefined safe states at startup and fault
  • Reverse polarity protection -protects the module from incorrect supply wiring


Application in industrial installations

The module fits tasks where digital signals must be distributed reliably over RS-485 in demanding environments.

  • Industrial automation
  • Remote control of relays and actuators
  • Distributed I/O in production plants
  • DIN-rail installations in cabinets


A robust and flexible choice for reliable digital signal distribution in industrial RS-485 networks.