Item number CHANN-THERM-VOLTA-CURRE-3

8-Channel Thermocouple/Voltage/Current Input Module RS-485 16-bit

8 x differential analog input channels
Voltage, current, thermocouple input
Thermocouple types J, K, T, E, R, S, B, N, C
16-bit resolution, 0.1% FSR accuracy
Sampling rate 10 Hz total
1 x RS-485, DCON protocol
Baud rate 1200-115200 bps
Open wire detection for thermocouple
3000VDC intra-module isolation
10-30VDC power input
72 x 123 x 35 mm
-25 to 75C (special components required)

325.62 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Type VoltageCurrentThermocouple
Resolution 16-bit
Range Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 VCurrent: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor)
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Intra-module Isolation 3000 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
Channels 8 Differential
Accuracy ±0.1% of FSR
Sampling Rate 10 Hz (Total)
Sensor Type Thermocouple: J, K, T, E, R, S, B, N, C
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line

Repeater Module

This repeater module is an analog input device for industrial measurement systems, converting signals from thermocouples, voltage or current into digital data via RS-485. It is used for accurate temperature and signal measurement in manufacturing plants and process industries.


8 differential channels · 16-bit resolution · RS-485 with DCON protocol · 3000VDC isolation


Features that ensure reliable measurement

  • Flexible input - supports voltage, current and thermocouple types J, K, T, E, R, S, B, N, C
  • High accuracy - 16-bit resolution with ±0.1% FSR
  • Individual channel configuration - each channel can be set up independently
  • Open wire detection - software selectable fault detection for thermocouples
  • Robust protection - EFT, ESD and surge protection according to IEC standards


Application areas in industry

The module is well suited for monitoring and control in environments requiring stable data transfer and high operational reliability.

  • Temperature monitoring in process plants
  • Industrial automation
  • Distributed data acquisition via RS-485
  • Measurement in harsh environments with DIN-rail mounting


A reliable choice for accurate analog signal processing in demanding industrial environments.