Item number 32-CHANN-OPEN-COLLE

32-Channel Open Collector Output Module RS-485 Modbus RTU, DCON

32 x Open Collector Output (Sink)
Load Voltage +5 ~ +40VDC
Load Current 200mA/channel
1 x RS-485, 1200~115200bps
Modbus RTU, DCON Protocol
Programmable Watchdog Timer
Power-on and Safe Value Support
Reverse Polarity Protection
Intra-module Isolation 2500VDC
10-48VDC Power Input
116 x 120 x 64 mm
-25 to +75C (special components required)

306.86 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Type Open Collector
Operating Temperature 25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Ports 1 x RS-485
Input Range +10 ~ +48 VDC
Consumption 1.0 W max.
Dimensions (mm) 116 x 120 x 64 (W x L x H)
Storage Temperature 40 ~ +80 °C
Humidity 10 ~ 95% RH, Non-condensing
Reverse Polarity Protection Yes
Intra-module Isolation 2500 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
Channels 32
Power-on Value Yes
Safe Value Yes
Sink/Source (NPN/PNP) Sink
Load Voltage +5 ~ +40 VDC
Load Current 200 mA/channel
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol Modbus RTU, DCON
Mode Burst, Continuous
Frequency 50 Hz
Bias Resistor No. Usually supplied by the RS-485 Master also add an optional tM-SG4 or SG-785.
EFT (IEC 61000-4-4) ±4 kV to Power
Surge (IEC 61000-4-5) ±2 kV for Power Line
Duty Cycle 0.1 ~ 99.9 %
Burst Count 1 ~ 65535

Repeater Module

This repeater module is designed for industrial control with 32 open collector output channels. It is used to drive external devices via digital sink signals in automation and process systems.


32 channels · RS-485 Modbus RTU/DCON · 200 mA/channel · -25 to +75°C


Features for reliable operation

  • 32 open collector outputs -provides high capacity for controlling many channels
  • Programmable watchdog -monitors communication and module for stable operation
  • Power-on and safe value -ensures predictable startup and fail-safe state
  • Reverse polarity protection -protects the module against incorrect supply wiring
  • High isolation of 2500 VDC -protects against noise and voltage spikes


Applications in industrial environments

The module suits applications where robust digital outputs need to be controlled precisely over RS-485.

  • Relay and actuator control
  • Automated production equipment
  • Distributed I/O systems
  • Monitoring and control in industrial networks


A reliable choice for demanding industrial output applications requiring many channels and robust communication.