Item number CHANN-COUNT-FREQU-ENCOD

8-Channel Counter/Frequency/Encoder Module RS-485, 32-bit

8-ch Up Counter or 4-ch Up/Down Counter
4-ch AB Phase Quadrature Counting
8-channel Frequency Counting Mode
32-bit Counter/Encoder Resolution
Frequency Accuracy +/-0.025% (1Hz-200kHz)
1 x RS-485, Modbus RTU/DCON
Baud Rate 1200-115200 bps
Battery Backup
Intra-module Isolation 3000 VDC
10-30VDC Input, 1.32W max
DIN-Rail Mounting
72 x 123 x 35 mm

222.44 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Type Counter, Frequency, or Encoder
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Intra-module Isolation 3000 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
Channels 4-channel Up/Down Counter (CW/CCW)4-channel Dir/Pulse Counter (Bi-direction)4-channel A/B Phase (Quadrature Counting)8-channel Up Counter8-channel Frequency
Sink/Source (NPN/PNP) Sink
ON Voltage Level +3.5 VDC ~ +30 VDC
OFF Voltage Level +1 VDC Max.
Battery Backup Yes
Encoder Mode CW/CCW, Dir/Pulse, AB Phase
Counter/Encoder Bits 32-bit
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±3 kV for Power Line
Counter Mode Up or Up/Down
Frequency Mode Yes

Repeater Module

This repeater module is designed for precise counting and frequency measurement in industrial automation systems. The module supports multiple operating modes and communicates via RS-485, making it well suited for integration into existing Modbus networks.


32-bit counter · 8 channels · RS-485 Modbus RTU/DCON · 10-30VDC


Flexible counting and measurement functions

  • Multiple operating modes -supports up/down counting, encoder and frequency measurement
  • 32-bit resolution -high accuracy for large count values
  • Individual channel configuration -each channel can be set independently
  • Battery backup -protects data during power loss
  • High isolation of 3000 VDC -protects against electrical noise and damage


Applications in industrial environments

The module suits applications where precise pulse counting or frequency measurement is required under demanding conditions.

  • Motor speed and encoder monitoring
  • Production counting on factory lines
  • Frequency measurement in process automation
  • Integration with Modbus-based SCADA systems


A robust and versatile solution for precise counting and frequency measurement in industrial applications.