Item number RTD-INPUT-MODUL-LED

RTD Input Module with LED Display, RS-485, Modbus RTU/DCON

1 x RTD input, Pt100/Pt1000/Ni120
16-bit resolution, 0.05% FSR accuracy
5-digit 7-segment LED display
1 x Dry contact input, 16-bit counter
2 x Open collector MOSFET output
700 mA/channel, sink type
1 x RS-485, Modbus RTU/DCON
Baud rate 1200-115200 bps
3000 VDC intra-module isolation
10-30VDC power input
72 x 123 x 35 mm (W x L x H)
-25 to 75C (special components required)

302.84 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type 5-Digit 7 Segment LED DisplayOpen Collector, MOSFETDry ContactRTD
Operating Temperature 25 ~ +75 °C
Resolution 16-bit
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Ports 1 x RS-485
Input Range +10 ~ +30 VDC
Consumption 1.2 W
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
Overload Protection 1.4 A
Short-circuit Protection Yes
Reverse Polarity Protection Yes
Intra-module Isolation 3000 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal±8 kV Air for Random Point
Channels 21
Accuracy ±0.05% of FSR
Sampling Rate 10 Hz
Overvoltage Protection ±30 VDC60 VDC±5 VDC
Safe Value Programmable
Sink/Source (NPN/PNP) SinkSource
ON Voltage Level Close to GND
OFF Voltage Level Open
Load Voltage +3.5 ~ +50 VDC
Load Current 700 mA/Channel
Power on Value Programmable
Baud Rate 1200 ~ 115200 bps
Sensor Type Pt100, Pt1000, Ni120
Resistance Measurement 3.2 kΩ max.
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol Modbus RTU, DCON
Open Wire Detection Yes
Frequency 50 Hz
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Max. Counts 65535 (16-bit)
3-wire RTD Lead Resistance Elimination Yes

RTD Repeater Module

This RTD repeater module is designed for accurate temperature measurement and signal conversion in industrial automation systems. The module converts RTD sensor signals into digital data via RS-485, making them available to higher-level SCADA and PLC systems. It is typically used where reliable temperature monitoring and electrical isolation are essential.


Pt100/Pt1000/Ni120 input · 16-bit resolution · RS-485 Modbus RTU/DCON · 3000 VDC isolation


Key Features and Benefits

  • High accuracy -0.05% FSR ensures reliable temperature readings
  • Built-in LED display -5-digit 7-segment display for local reading
  • Digital I/O -dry contact input and two MOSFET outputs for control
  • Robust protection -ESD, EFT and surge protection per IEC standards
  • 3-wire lead resistance elimination -ensures accurate measurement regardless of cable length


Application Areas

The module is suited for industrial environments requiring reliable temperature monitoring and remote control via RS-485 networks.

  • Process monitoring in production facilities
  • Temperature control in HVAC systems
  • Automated measurement in power supply systems
  • Distributed I/O in industrial networks


A robust and accurate choice for industrial temperature measurement and signal conversion.