Item number RTD-REPEA-MODUL-RS

1-ch RTD Input Module with 1-ch DI and 2-ch DO, RS-485, DCON/Modbus RTU

1-channel RTD input via RS-485
Pt100, Pt1000, Ni120 sensors
16-bit resolution, 10 Hz sampling
Accuracy +/-0.05% of FSR
1 x Digital input, dry contact
2 x Open collector output, 700mA
Modbus RTU, DCON protocol
Open wire detection
3000VDC intra-module isolation
10-30VDC input, 0.6W
72 x 123 x 35 mm
-25 to +75C (special components required)

268.00 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type Dry ContactOpen Collector, MOSFETRTD
Operating Temperature 25 ~ +75 °C
Resolution 16-bit
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication
Ports 1 x RS-485
Input Range +10 ~ +30 VDC
Consumption 0.6 W
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
Overload Protection 1.4 A
Short-circuit Protection Yes
Reverse Polarity Protection Yes
Intra-module Isolation 3000 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal±8 kV Air for Random Point
Channels 21
Accuracy ±0.05% of FSR
Sampling Rate 10 Hz
Overvoltage Protection ±30 VDC60 VDC±120 VDC
Safe Value Programmable
Sink/Source (NPN/PNP) SinkSource
ON Voltage Level Close to GND
OFF Voltage Level Open
Load Voltage +3.5 ~ +50 VDC
Load Current 700 mA/Channel
Power on Value Programmable
Baud Rate 1200 ~ 115200 bps
Sensor Type Pt100, Pt1000, Ni120
Resistance Measurement 3.2 kΩ max.
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol Modbus RTU, DCON
Open Wire Detection Yes
Frequency 50 Hz
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Max. Counts 65535 (16-bit)
3-wire RTD Lead Resistance Elimination Yes

RTD Repeater Module

This repeater module converts and retransmits RTD temperature signals into a reliable RS-485 Modbus signal. It is used for accurate temperature monitoring in industrial installations where long signal paths or electrical noise require robust signal processing.


1 x RTD channel · Pt100/Pt1000/Ni120 · 16-bit resolution · RS-485 Modbus RTU/DCON


Features that ensure stable temperature measurement

  • High accuracy -measures with a precision of +/-0.05% of FSR
  • Open wire detection -automatically warns of sensor lead breaks
  • 3-wire lead resistance elimination -removes errors from long cable runs
  • Digital I/O -includes dry contact input and two open collector outputs
  • Strong protection -overvoltage, overload, and short-circuit protected


Application areas

The module is well suited for industrial environments where temperature data must be reliably collected over distance via RS-485.

  • Process monitoring in production plants
  • HVAC and energy management systems
  • Machine monitoring and maintenance
  • Distributed temperature measurement in SCADA systems


A robust and accurate choice for reliable RTD temperature measurement in demanding industrial environments.