Item number MODUL-8X-DIGIT-INPUT

I/O Module 8x Digital Input, 3x AC-SSR Relay Output, RS-485

8 x Digital Input, Wet Contact
Sink/Source (NPN/PNP)
3 x AC-SSR Relay Output (Form A)
Contact Rating 24-265VAC @ 1A
1 x RS-485, DCON Protocol
Baud Rate 1200-115200 bps
Counter 16-bit, up to 65535
Programmable Watchdog Timer
DIN-Rail Mounting
10-30VDC
72 x 123 x 35 mm
-25 to 75C (special components required)

176.88 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type I/O LED IndicatorWet ContactAC-SSR
Operating Temperature 25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication11 x Digital Input/Relay Output
Ports 1 x RS-485
Input Range +10 ~ +30 VDC
Consumption 1.0 W
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
Reverse Polarity Protection Yes
Intra-module Isolation 3750 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal±8 kV Air for Random Point
Channels 3 (Form A)8
Input Impedance 3 kΩ
Overvoltage Protection ±35 VDC
Safe Value Programmable
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +1 VDC max.
OFF Voltage Level +4 ~ +30 VDC
Power on Value Programmable
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol DCON
Contact Rating 24 ~ 265 VAC @ 1A
Operate Time 1/2 cycle + 1 ms
Release Time 1/2 cycle + 1 ms
Electrical Endurance Long Life, No Arcing, No Bounce, No Switching Noise
Leakage Current 1.5 mA
Frequency 100 Hz
EFT (IEC 61000-4-4) ±2 kV for Power Line
Max. Counts 65535 (16-bit)
Min. Pulse Width 5 ms

I/O Module

This I/O module is designed for industrial data acquisition and control, converting digital signals into relay outputs. It communicates via RS-485 and is well suited for demanding automation environments requiring high reliability.


8 x Digital Input · 3 x AC-SSR Output · RS-485 DCON · DIN-Rail


Features and Benefits

  • Digital inputs -8 channels with wet contact and sink/source configuration
  • AC-SSR relay outputs -3 channels with no mechanical wear, arcing, or noise
  • RS-485 communication -stable DCON protocol with adjustable baud rate
  • Programmable watchdog -ensures stable operation during communication faults
  • Robust protection -high ESD and EFT immunity for harsh environments


Applications

The module fits tasks where digital signals and relay control need to be integrated into a central automation system.

  • Industrial process control
  • Building automation
  • Machine monitoring
  • Remote equipment control via RS-485 networks