Item number MODUL-DIGIT-INPUT-RELAY

I/O Module 4 x Digital Input, 4 x Relay Output, RS-485 Modbus RTU

4 x Digital Input, Wet Contact
4 x Relay Output (2 x Form A, 2 x Form C)
Form A: 16A @ 250VAC, 10A @ 30VDC
1 x RS-485, 1200-115200 bps
Modbus RTU, DCON Protocol
Counter up to 65535 (16-bit)
Programmable Watchdog Timer
Power on / Safe Value Programmable
Reverse Polarity Protection
10-30VDC, 1.8W
72 x 123 x 35 mm
-25 to 75C (special components required)

166.16 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type Wet ContactI/O LED IndicatorPower Relay
Operating Temperature 25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status 1 x Power and Communication8 x Digital Input/Relay Output
Ports 1 x RS-485
Input Range +10 ~ +30 VDC
Consumption 1.8 W
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
Reverse Polarity Protection Yes
Intra-module Isolation 3750 VDC
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal±8 kV Air for Random Point
Channels 44 (2 x Form A, 2 x Form C)
Input Impedance 10 kΩ
Overvoltage Protection ±70 VDC
Safe Value Programmable
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +4 VDC max.
OFF Voltage Level +10 ~ +50 VDC
Power on Value Programmable
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol Modbus RTU, DCON
Contact Material Silver Tin Alloy
Contact Rating Form A: 16 A @ 250 VAC10 A @ 30 VDCForm C:NO: 10 A @ 250 VACNC: 6 A @ 250 VAC
Operate Time 10 ms
Release Time 5 ms
Electrical Endurance 1 x 10^5 ops.
Mechanical Endurance 1 x 10^7 ops.
Frequency 100 Hz
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±3 kV for Power Line
Max. Counts 65535 (16-bit)
Min. Pulse Width 5 ms

I/O Module

This I/O module is designed for industrial monitoring and control via RS-485. It combines digital inputs with relay outputs, making it ideal for automation tasks where reliable communication and robust operation are essential.


4 x Digital Input · 4 x Relay Output · RS-485 Modbus RTU/DCON · -25 to 75°C


Features that make a difference

  • Digital inputs -supports wet contact with counting up to 65535
  • Relay outputs -combination of Form A and Form C relays for flexible control
  • RS-485 communication -stable Modbus RTU/DCON connection up to 115200 bps
  • Programmable watchdog -ensures automatic recovery from communication failure
  • Robust protection -built-in EFT, ESD and surge protection for long service life


Application areas

The module suits industrial environments where reliable I/O control over long distances is required.

  • Process monitoring
  • Building automation
  • Remote equipment control
  • Distributed data acquisition


A robust and flexible choice for industrial I/O control via RS-485.