Item number CANOP-MODUL-DIGIT-INPUT

CANopen I/O Module, 4 Digital Input / 4 Relay Output, DIN-Rail

CANopen protocol CiA 301/401
4 x Digital Input (Wet Contact)
4 x Relay Output (Form A)
Baud Rate 10k - 1Mbps
Isolation 3000VDC / 2500Vrms
Built-in 120 Ohm Terminal Resistor
Hardware Watchdog Timer
3 Status LEDs (PWR/RUN/ERR)
DIN-Rail Mounting
Power Consumption: 1.7W
33 x 99 x 78 mm
-25/+75C (special components required)

219.76 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Type Form A (SPST-NO)Wet Contact
Operating Temperature -25 ~ +75 °C
Terminal Resistor Built-in 120Ω
Watchdog Timer Hardware watchdog
Status 3 LEDs to PWR, RUN and ERR
Consumption 1.7 W
Dimensions (mm) 33 x 99 x 78 ( W x L x H )
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Channels 4
Input Impedance 3kΩ, 0.3W
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +3.5 ~ +30 VDC
OFF Voltage Level +1 VDC Max
Baud Rate 10 k ~ 1 M
Protocol CiA 301 v4.02, CiA 401 v2.1
Operate Time 10ms max
Release Time 5ms max
Node ID 1 ~ 99
No. of PDOs 10 RxPDO , 10 TxPDO
Error Control Node Guarding protocol / Heartbeat Producer
NMT Slave
EMCY Message Yes
PDO Mode Event-triggered, remotely-requested, Cyclic and acyclic SYNC

CANopen I/O Controller

This CANopen I/O controller provides digital input and relay output channels for industrial CAN bus networks. It is designed for reliable monitoring and control in automation systems following the CiA 301 and CiA 401 device profiles. The DIN-rail housing makes it easy to integrate into existing control cabinets.


4 Digital Inputs · 4 Relay Outputs · CiA 301/401 Protocol · DIN-Rail Mount


Key Features and Benefits

  • Wet Contact Inputs - detects voltage signals from 3.5 to 30 VDC
  • Form A Relay Outputs - switches loads with fast 10ms operate time
  • Built-in Terminal Resistor - simplifies CAN bus termination without extra wiring
  • Galvanic Isolation - protects the controller with 3000VDC and 2500Vrms isolation
  • Hardware Watchdog - ensures automatic recovery from communication faults


Typical Applications

The controller is suitable for distributed I/O tasks in industrial CAN bus systems.

  • Factory automation control cabinets
  • Machine monitoring and status reporting
  • Remote switching of pumps, valves and motors
  • Distributed control in CANopen networks


A robust, isolated CANopen I/O solution for demanding industrial environments.