Item number GATEW-MODUL-6X-DIGIT

I/O Gateway Module with 6x Digital Input, 6x Relay Output, MQTT/Modbus TCP

6 x Digital Input (Dry/Wet Contact)
6 x Power Relay Output (Form A)
MQTT and Modbus TCP protocols
2 x RJ45 10/100 Ethernet Switch Ports
Built-in Web Server
Programmable Watchdog Timer
LAN Bypass Function
EMC Protection (EFT, ESD, Surge)
Metal Casing, DIN-Rail or Wall Mount
12-48VDC Power Input
-25-75C (special components required)
97 x 120 x 42 mm

364.48 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail or Wall Mounting
Type Dry ContactWet ContactPower Relay, Form A (SPST N.O.)
Operating Temperature -25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet, I/O
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
Consumption 3.6 W max.
Dimensions (mm) 97 x 120 x 42 (W x L x H)
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
Channels 6
Input Impedance 10 kΩ
Overvoltage Protection +70 VDC
Safe Value Programmable
Powered from Terminal Block +12 ~ +48 VDC
Sink/Source (NPN/PNP) Dry: SourceWet: Sink/Source
ON Voltage Level Dry: Close to GNDWet: +10 ~ +50 VDC
OFF Voltage Level Dry: OpenWet: +4 VDC max.
Effective Distance 500m max.
Power on Value Programmable
Protocol MQTT 3.1Modbus TCP
Casing Metal
Contact Rating 5 A @ 250 VAC/24 VDC (Resistive Load)
Operate Time 10 ms max.
Release Time 5 ms max.
Electrical Endurance 10^5 ops.
Mechanical Endurance 2 × 10^7 ops.
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±2 kV for Power Line
LAN bypass Yes
Built-in Web Server Yes

Gateway Module

This gateway module connects digital I/O signals to Ethernet networks using MQTT and Modbus TCP. It is designed for industrial automation systems that require reliable remote monitoring and control of dry and wet contact inputs together with relay outputs.


6 x Digital Input · 6 x Relay Output · MQTT / Modbus TCP · -25 to 75°C Operation


Key Features for Reliable Industrial Communication

  • Dual Protocol Support - communicates via MQTT and Modbus TCP for flexible integration
  • Built-in Web Server - allows configuration and monitoring directly from a browser
  • Programmable Watchdog - automatically resets communication in case of failure
  • LAN Bypass - keeps network traffic flowing even if the module loses power
  • Wide Protection Range - EFT, ESD and surge protection ensure stable operation in harsh environments


Typical Applications

The module suits environments where digital signals must be monitored or controlled remotely over an Ethernet network.

  • Factory automation and machine monitoring
  • Building and facility management systems
  • Remote control of pumps, valves and motors
  • Distributed I/O for SCADA and PLC systems


A robust and flexible I/O gateway for industrial Ethernet networks.