Item number LOG3F-D-E

Single-Circuit Smart Power Meter with Modbus, DIN-Rail Mount

DIN-rail single-circuit power meter
True RMS, 128 samples per cycle
1P2W, 1P3W, 3P3W or 3P4W systems
Input 20-400VAC L-N, 35-600VAC L-L
333mV CT or Rogowski coil input
1 x RS-485, Modbus RTU, 115200bps
THD, unbalance, demand, max/min
2MB flash data logging
128 x 64 LCD, white backlight
Pulse output, open collector 30VDC
85-264VAC or 100-300VDC
72 x 87.5 x 58.7 mm

Call +45 56 66 20 20 for price
Quantity
On the way in
file_download DOWNLOADS

Specifications

Flash 2MB Flash ROM with no battery life limitation
Kabinet Black flame-retardant ABS
Montering 35mm DIN-skinne (EN50022)
Protokol Modbus RTU
Rækkevidde 1200m (RS-485)
Skærm 128 x 64 dot-matrix LCD with white backlight, refresh rate 0.5 seconds
Strømforbrug AC: max. 5VA; DC: max. 2W
Strømforsyning 85-264V AC, 50/60Hz or 100-300V DC
Weight 195 g
Dimensioner 72 x 87.5 x 58.7 mm (W x D x H)
COM ports 1 x RS-485; device address 1-247; 8 data bits; parity none, even or odd; 1 or 2 stop bits; response time under 50ms; max. 32 connected devices
Serial Baud Rate Up to 115200bps
LED indicator TX, RX, PO and TOU
Measuring Parameters THD for voltage and current, three-phase voltage and current unbalance, phase angle of voltage and current, max./min. values with timestamp, total CO₂ weight calculated from energy consumption
Sampling Rate 128 samples per cycle
Number of circuits Single circuit (1 measuring circuit)
Current sensor Conventional CT with voltage output (0-333mV) or Rogowski coil (333mV), depending on variant
Electrical system 1P2W, 1P3W, 3P3W or 3P4W with balanced or unbalanced load
Voltage input 20-400V AC (L-N), 35-600V AC (L-L)
Measuring frequency 45-65Hz
Measuring principle True RMS measurement with 128 samples per cycle
Max. CT primary current CT primary 1-9999A, CT secondary 333mV
PT ratio PT primary 100-1200000V, PT secondary 50-500V
Overload capacity Voltage: 2 times rated voltage continuously, 2500V for 1 second; Current: 2 times rated current continuously, 20 times rated current for 1 second
Demand Demand for current, active, reactive and apparent power; fixed or sliding block calculation; period 1-60 minutes; max. demand with timestamp
Automatic wiring correction Supported under specified wiring and phase angle conditions
Data logging Selected measuring parameters are logged at a configurable interval of 1-32767 seconds, minutes, hours or days; circular recording when memory is full; approx. 40,300 records or 28 days with ten 4-byte data points per minute; configured and read out via c
Event records Up to 16 records of abnormal events with source, status, measured value, date and time
Pulse output Open collector, max. 30V DC and 30mA, max. 1000Hz; import/export of active or reactive energy
Real-time clock Perpetual calendar with year, month, day, hour, minute and second

DIN-Rail Modbus Smart Power Meter for Single Circuits

The DIN-rail smart power meter measures electrical parameters and energy on a single circuit and sends the data to a control or monitoring system over Modbus RTU. It is made for panel builders and system integrators who need energy monitoring inside a control cabinet. It is available with an input for a conventional 333mV current transformer (SPM-D01-M) or for a Rogowski coil (SPM-D01-R).

Two Current Sensor Options for New and Existing Installations

The CT version uses standard voltage-output current transformers, so it fits panels that already have them. The Rogowski coil version uses a flexible coil that can be placed around a conductor, which helps where a solid-core CT cannot be fitted. Primary CT and PT ratios are configurable, so the meter can be used on low-voltage circuits and with voltage transformers on higher-voltage systems.

Power Quality, Demand and Event Data

True RMS measurement covers single-phase and three-phase systems with balanced or unbalanced loads. Besides basic values, the meter reports harmonic distortion, unbalance, phase angle and demand, with maximum and minimum values time-stamped. It also stores up to 16 abnormal-event records and calculates CO2 emission from energy consumption.

Onboard Logging and RS-485 Communication

The 2MB flash memory records selected parameters at configurable intervals and overwrites the oldest data when full. Logs are configured and read over the RS-485 port, which supports up to 32 devices on one bus. A pulse output can be assigned to import or export energy, for use with counters or PLC inputs.