Item number 16-CHANN-DIGIT-INPUT-9

16-Channel Digital Input Ethernet Module, Modbus TCP/UDP, DIN-Rail

16 x Digital Input, Wet Contact
Sink/Source (NPN/PNP) type
Modbus TCP, Modbus UDP protocol
1 x RJ-45 10/100 Base-TX
Built-in Web Server
Isolation: Ethernet 1500VDC, I/O 2500VDC
Max counts 4,294,967,295 (32-bit)
Frequency 500 Hz, min pulse 1 ms
ID, Password and IP Filter security
10-30VDC
72 x 123 x 35 mm
-25 to +75C (special components required)

218.42 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
Type Wet Contact
Operating Temperature 25 ~ +75 °C
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet
Ports 1 x RJ-45, 10/100 Base-TX
Consumption 2.1 W (max.)
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Storage Temperature 30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal ±8 kV Air for random point
Channels 16
Input Impedance 10 kΩ
Overvoltage Protection +70 VDC
Powered from Terminal Block +10 ~ +30 VDC
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level +10 ~ +50 VDC
OFF Voltage Level +4 VDC (max.)
Protocol Modbus TCP, Modbus UDP
Frequency 500 Hz
2-way Isolation Ethernet: 1500 VDCI/O: 2500 VDC
EFT (IEC 61000-4-4) ±4 kV for Power Line
Max. Counts 4,294,967,295 (32-bit)
Min. Pulse Width 1 ms
Access Control ID, Password and IP Filter
Built-in Web Server Yes

Digital I/O Module

This digital I/O module is designed for monitoring digital signals via Ethernet in industrial environments. The module provides 16 channels for wet contact inputs and communicates via Modbus TCP/UDP, making it well suited for integration into existing automation systems.


16 x Digital Input · Modbus TCP/UDP · 2-way Isolation · DIN-Rail Mounting


Features that make the difference

  • High-precision counting -supports up to 4,294,967,295 counts with 32-bit resolution
  • Sink/Source support -compatible with both NPN and PNP configurations
  • Built-in web server -easy configuration and monitoring directly via browser
  • Robust isolation -1500 VDC on Ethernet and 2500 VDC on I/O protects against noise and overvoltage
  • Security access -ID, password and IP filtering ensure controlled access


Application areas

The module is suited for industrial applications where reliable monitoring of digital signals over a network is required.

  • Factory automation
  • Sensor and contact monitoring
  • Building management
  • Process control and data acquisition


With robust isolation, high channel density and flexible Modbus communication, this module is a reliable choice for industrial digital I/O monitoring.