Item number 16-CHANN-AC-DIGIT-2

16-Channel AC Digital Input Ethernet Module with PoE, Modbus TCP/UDP

16 x AC Digital Input, Wet Contact
Sink/Source (NPN/PNP)
ON: 80-250VAC / +-100-250VDC
2 x RJ45 10/100 Switch Ports
PoE IEEE 802.3af, Class 1
LAN Bypass Function
Modbus TCP/Modbus UDP
2500VDC I/O Isolation
Built-in Web Server
12-48VDC (Terminal Block), 2.9W max
97 x 130 x 38 mm
-40 to +75C (special components required)

420.76 €
Excl. VAT
Quantity
On the way in
file_download DOWNLOADS

Specifications

Installation DIN-Rail Mounting
PoE yes
Type Wet Contact
Operating Temperature 40 ~ +75°C
Watchdog Timer Module, Communication (Programmable)
Status Run, Ethernet, I/O, PoE
Ports 2 x RJ-45, 10/100 Base-TX, Switch Ports
Consumption 2.9 W (max.)
Dimensions (mm) 97 x 130 x 38 (W x L x H)
Storage Temperature 30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
Reverse Polarity Protection Yes
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal ±8 kV Air for random point
Channels 16
Input Impedance 150 kΩ
Overvoltage Protection 300 VAC
Powered from Terminal Block +12 ~ +48 VDC
Sink/Source (NPN/PNP) Sink/Source
ON Voltage Level 80 ~ 250 VAC±100 ~ ±250 VDC
OFF Voltage Level 30 VAC (max.)±30 VDC (max.)
Protocol Modbus TCP, Modbus UDP
Powered from PoE IEEE 802.3af, Class1
Frequency 100 Hz
2-way Isolation I/O: 2500 VDC
EFT (IEC 61000-4-4) ±4 kV for Power Line
Max. Counts 4,294,967,295 (32-bit)
Min. Pulse Width 5 ms
LAN bypass Yes
Access Control ID, Password and IP Filter
Built-in Web Server Yes

AC Digital Input Module

This AC Digital Input module provides 16 channels for monitoring AC voltage signals in industrial networks. The module is built for reliable operation in harsh environments and integrates easily via Ethernet with support for Modbus TCP and UDP.


16 x AC Digital Input · PoE IEEE 802.3af · Modbus TCP/UDP · -40 to +75°C


Features that ensure reliable operation

  • Wet Contact inputs -supports Sink/Source (NPN/PNP) configuration
  • PoE powered -receives power directly through the network cable
  • LAN Bypass -maintains network connectivity during power loss
  • 2-way isolation -2500 VDC protects against noise and transients
  • Built-in web server -easy configuration and monitoring without extra software


Applications in industrial networks

The module is well suited for monitoring AC signals in harsh industrial environments requiring stable data acquisition.

  • Process monitoring in factory automation
  • Monitoring of alarms and status signals
  • Building automation and technical monitoring
  • Remote measurement tasks over Ethernet


With robust isolation, PoE power and wide operating temperature, this module is the right choice for harsh industrial environments.